Everything you need to carry out efficient servicing and commissioning of heating systems using the testo 330i flue gas analyzer – in one compact set.
Details
Product Description
The testo 330i flue gas analyzer combines the proven measuring technology of the preceding model testo 330 LL with a revolutionary new method of operation: operation independent of measuring location via smartphone, a sturdy testoFix probe holder and paperless documentation. This instrument embodies the current trends in flue gas measurement.
The centrepiece of the set is the testo 330i flue gas analyzer with H2-compensated CO sensor. The flue gas analyzer is therefore also approved for the official acceptance testing of heating systems.
Operation of the flue gas analyzer and the display of readings are implemented independently of the measuring location via the testo 330i App on your smartphone or tablet. Here, you can make adjustments to the measuring instrument, analyze the flue gas values, enter customer data and create measurement protocols. You can then add comments or photos of the system to the protocols, and send them to the customer or your office via e-mail.
Requirement: iOS 7.1 / Android 4.3 or newer. Mobile end device with Bluetooth 4.0.
The testo 330i flue gas analyzer also has the following impressive features
Also included in the set: a modular flue gas sampling probe (180 mm) with a 65 cm long, extra-flexible hose and a 190 mm long combustion air temperature probe.
The testo Fix probe holder is included in the set, which enables the probes to be securely attached to the flue gas duct quickly and easily. This global innovation also serves as a fall-proof suspension system for the testo 330i flue gas analyzer. A mains unit and the practical system case, in which all set components can be stowed away compactly and safely, complete this set.
At the core of the measuring technology of the testo 330i are the two long-life sensors for measuring O2 and CO. An NO sensor is optionally available. With the testo 330i, flue gas and draught are measured in parallel – therefore you always have an overview of all relevant readings on a screen in the testo 330i App.
You can also use the testo 330i flue gas analyzer to measure the gas supply on gas boilers. Measure the gas flow and gas resting pressure to ensure that a gas boiler can be commissioned properly. In conjunction with the manufacturer’s specifications concerning the nozzle pressure, the results of this measurement will enable you to tailor the output of the boiler to the home’s actual heat requirement.
In balanced flue systems, you can use the testo 330i to find out whether there is a leak in the flue gas system. For this, simply measure the O2 content of the combustion air in the dual wall clearance. This way, you can ensure that no flue gas is getting into the combustion air supply. This prevents damage due to condensate or impairment of the combustion process.
Do you have any questions?
We would be more than happy to help you.
General technical data | |
---|---|
Weight | 720 g (excluding battery) |
Dimensions | 270 x 160 x 57 mm |
Operating temperature | -5 to +45 °C |
Power supply | Rech. batt. block 3.7 V / 2.6 Ah; Mains unit 6 V / 1.2 A (optional) |
System requirements | requires iOS 7.1 or newer; requires Android 4.3 or newer; requires mobile end device with Bluetooth 4.0 |
Maximum memory | 500000 readings |
Storage temperature | -20 to +50 °C |
Differential Pressure – Piezoresistive | |
---|---|
Measuring range | 0 to 300 hPa |
Accuracy | ±0.5 hPa (0.0 to +50.0 hPa)
±1 % of mv (+50.1 to +100.0 hPa) ±1.5 % of mv (Remaining Range) |
Resolution | 0.1 hPa |
Flue gas O₂ | |
---|---|
Measuring range | 0 to 21 Vol.% |
Accuracy | ±0.2 Vol.% |
Resolution | 0.1 Vol.% |
Flue gas CO (with H₂-compensation) | |
---|---|
Measuring range | 0 to 8000 ppm |
Accuracy | ±10 ppm or ±10 % of mv (0 to 200 ppm)
±20 ppm or ±5 % of mv (201 to 2000 ppm) ±10 % of mv (2001 to 8000 ppm) |
Resolution | 1 ppm |
CO determination (with H₂-compensation), automatic dilution | |
---|---|
Measuring range | 0 to 30000 ppm |
Accuracy | ±200 ppm or ±20 % of mv (0 to 30000 ppm) |
Resolution | 1 ppm |
Flue gas NO | |
---|---|
Measuring range | 0 to 3000 ppm |
Accuracy | ±5 ppm (0 to 100 ppm)
±5 % of mv (101 to 2000 ppm) ±10 % of mv (2001 to 3000 ppm) |
Resolution | 1 ppm |
Option
Differential Pressure flue gas Draught – Piezoresistive | |
---|---|
Measuring range | -9.99 to +40 hPa |
Accuracy | ±0.02 hPa or ±5 % of mv (-0.50 to +0.60 hPa)
±0.03 hPa (+0.61 to +3.00 hPa) ±1.5 % of mv (3.01 to +40.00 hPa) (the greater value applies) |
Resolution | 0.01 hPa |
Temperature | |
---|---|
Measuring range | -40 to +1200 °C |
Accuracy | ±0.5 °C (0.0 to +100.0 °C)
±0.5 % of mv (Remaining Range) |
Resolution | 0.1 °C (-40 to +999.9 °C)
1 °C (Remaining Range) |
dependent on the thermocouple
Flue gas degree of effectivity, Eta (calculated) | |
---|---|
Measuring range | 0 to 120 % |
Resolution | 0.1 % |
Flue gas loss (calculated) | |
---|---|
Measuring range | 0 to 99.9 % |
Resolution | 0.1 % |
Flue gas CO₂ calculation (calculated from O₂) | |
---|---|
Measuring range | Display range 0 to CO₂ max |
Accuracy | ±0.2 Vol.% |
Resolution | 0.1 Vol.% |